Normal application for most surfaces will require 1 gallon per 100 square feet (16 wet mils = 10 dry mils). Where additional protection is necessary, two coats at 120 square feet per gallon per coat will provide an overall coverage of 60 square feet per gallon (27 wet mils = 17 dry mils).
Surface PreparationAll surfaces to be coated must be clean, dry and free of loose particles, oils, grease or any substance that would interfere with proper bond. A careful inspection of the surface should be made to detect any signs of damage or defects, and all repairs should be completed before application begins.
Most non-porous, non-metallic surfaces will not need to be primed. Metals should be primed with Polaprime 21. Porous surfaces should be primed with Polaprime 2. Once preparation is completed and any primers are thoroughly dry, ANDEK FIREGARD may be applied.
ApplicationANDEK FIREGARD may be applied using brush, roller or airless spray technique. Normal application for most surfaces will require 1 gallon per 100 square feet (16 wet mils = 10 dry mils). Where additional protection is necessary, two coats at 120 square feet per gallon per coat will provide an overall coverage of 60 square feet per gallon (27 wet mils = 17 dry mils).
Spray ApplicationFor spray application use 30:1 airless pump, 3/8″ short hose and 33 tip
Clean upTools may be cleaned using water while the product is still wet. If the material has dried, a suitable cleaning solvent may be used.